• Cabinets: Schneider Electric, indicative type Kaedra IP65. Lock included.
• Switching equipment: Schneider Electric.
• Terminal blocks are not included.
• Cable entry/exit from the bottom or top, through gland-plates without knock-outs or cable glands.
• Conductor routing inside the panels is carried out within plastic ducts.
• The internal wiring will be done with H05V-K and H07V-K type cables. The cross-section of the main busbar system and the internal conductor cross-sections have been calculated according to the rated currents of the switching equipment.
Busbar system >250A: DIN 43671, Cu ETP EN13601, N:50%
SINGLE-PHASE ELECTRICAL PANEL
Material Code – Brand – Material Description – Supplier Code – Quantity
After the completion of their construction, the panels will undergo the routine tests specified by standard IEC 61439-1, which include:
• Inspection of the panel and electrical operation test (automations).
• Dielectric test under voltage 1890V / 50Hz.
• Verification of protective parts and electrical continuity of the protective circuit.
Each panel will be accompanied by a routine test certificate according to IEC 61439-1 and multiline diagrams in printed and/or electronic form (dwg files).