Your Cart

Three-phase battery

Three-phase battery
Three-phase battery
Three-phase battery
Three-phase battery
Three-phase battery
Three-phase battery
Three-phase battery
  • Stock: In Stock
  • Model: 3f
607,60€
Ex Tax: 490,00€

Description

1. Materials–Construction–Notes

  • Cabinets: Schneider Electric, indicative type Kaedra IP65. Lock included.
  • Switching equipment: Schneider Electric.
  • Terminal blocks are not included.
  • Cable entry/exit from the bottom or top via gland-plates without knock-outs or cable glands.
  • Conductor routing inside the panels is carried out within plastic ducts.
  • Internal wiring will be done with H05V-K and H07V-K type cables. The cross-section of the main busbar system and the internal cable cross-sections have been calculated according to the rated currents of the switching equipment.
  • Busbar system >250A: DIN 43671, Cu ETP EN13601, N:50%


THREE-PHASE ELECTRICAL PANEL

Material CodeBrandMaterial DescriptionSupplier Code Quantity
1010688SCHNEIDER ELECTRICFuse holder 10x38mm 3P 25A L+NA9N156581
1000368SCHNEIDER ELECTRICLED rail indicator red 230VACA9E183203
1001020SCHNEIDER ELECTRICRail switch 4P 40A 400VACA9S654401
1001000SCHNEIDER ELECTRICMiniature circuit breaker C40A 6kA 4P 400VACA9F744401
1011065SCHNEIDER ELECTRICMiniature circuit breaker C32A 6kA 4P 400VACA9F744321
1000991SCHNEIDER ELECTRICResidual current circuit breaker (RCCB) 40A 30mA 4P Type A 10kA 400VA9R214401
1010947SCHNEIDER ELECTRICSurge arrester T2+T3 4P 8kAA9L086001
1011064SCHNEIDER ELECTRICMiniature circuit breaker C20A 6kA 4P 400VACA9F744201
1010568SCHNEIDER ELECTRICWall-mounted panel, 3 rows, 54 modules, plastic, IP65, with door134361
1010575SCHNEIDER ELECTRICPanel lock139481



2. Certificates–Tests–Documentation

  • After construction is completed, the panels will undergo the routine tests specified by IEC 61439-1, which include:
  • Inspection of the panel and electrical operation test (automation)
  • Dielectric test under voltage 1890V / 50Hz.
  • Verification of protective parts and continuity of the protective circuit.
  • Each panel will be accompanied by a routine test certificate according to IEC 61439-1 and multiline diagrams in printed and/or electronic form (dwg files).